APC Switched Rack PDU (AP8000)

APC Switched Rack PDU (AP8000)

to get values for

Total Device Load (KW)

Phase L1 Load (A)

Bank 1 Load (A)

Bank 2 Load (A)

APC has a Management GUI where list these values.

Example for OIDs and example values 
Load Status Overload Range
.1.3.6.1.4.1.318.1.1.26.4.1.1.8.1 = INTEGER: 40 4.0 KW >rPDU2DeviceConfigNearOverloadPowerThreshold.1 - Warning
.1.3.6.1.4.1.318.1.1.26.4.1.1.9.1 = INTEGER: 50 5.0 KW rPDU2DeviceConfigOverloadPowerThreshold.1 - Critical

.1.3.6.1.4.1.318.1.1.26.4.3.1.5.1 = INTEGER: 300 = 3 KW The power consumption of the Rack PDU load in hundredths of kilowatts
.1.3.6.1.4.1.318.1.1.26.4.3.1.6.1 =450 Peak consumption 4.5 KW

Load Status Overload Range Per Bank (1 2 3)
Triger values for Warning  .1.3.6.1.4.1.318.1.1.26.6.1.1.6.1 = INTEGER: 19 Amp
Triger values for Critical    .1.3.6.1.4.1.318.1.1.26.6.1.1.7.1 = INTEGER: 24Amp

Phase L1 Load    .1.3.6.1.4.1.318.1.1.12.2.3.1.1.2.1 = GAUGE32: 160= 16 A
Bank 1 Load        .1.3.6.1.4.1.318.1.1.12.2.3.1.1.2.2 = GAUGE32: 900 = 9 A
Bank 2 Load        .1.3.6.1.4.1.318.1.1.12.2.3.1.1.2.3 = GAUGE32: 60 = 6 A

Test values before applying.

Transforms added For Total Load, phase and Banks 1,2