Just a forewarning and cautionary tale to those out there who use Emerson Network Power UPSs and poll them through Solarwinds; it appears that the newer webcards have significantly cut down on the available OIDs compared to the older models. The most notable change is the removal of OID 1.3.6.1.2.1.33.1.2.4.0 (upsEstimatedChargeRemaining). You're now limited to polling upsEstimatedMinutesRemaining. I'm sure this is a bit of a niche case, but I figured I'd put it out there.
- N